    EPEVER solar mppt system

    Good day all,

    Hope you all had a great weekend.

    My father in law has installed a EPEVER MPPT system with two 200amp batteries and 5 x180watt panels.

    Only problems is the max charge that goes into the battery is 12.6V, i’ve checked with the multimeter and nothing over 12.6V goes into the battery.

    Any advise on how to set it up so we can get a decent charge out of it.

    Thanks

    J

  2. #2
    p38arover's Avatar
    p38arover is offline Major part of the heart and soul of AULRO.com
    Administrator
    I'm here to help you!
    Gold Subscriber
    Join Date
    Jan 1970
    Location
    Western Sydney
    Posts
    30,160
    Total Downloaded
    0
    Hi Jan,

    That's basically the battery voltage - that's not the charge going in.

    What current is flowing into the batteries? Switch the multimeter to the 10A (or preferably greater range) and connect in series with one of the leads to the battery.

    Are the panels in series or in parallel? I assume in parallel.

    Are the batteries in series or parallel? By the voltage I assume in parallel.
    Ron B.
    VK2OTC

    2003 L322 Range Rover Vogue 4.4 V8 Auto
    2007 Yamaha XJR1300
    Previous: 1983, 1986 RRC; 1995, 1996 P38A; 1995 Disco1; 1984 V8 County 110; Series IIA



    RIP Bucko - Riding on Forever

  3. #3
    Join Date
    Feb 2007
    Location
    Perth
    Posts
    3,807
    Total Downloaded
    0
    Might help if you state what model the Epever regulator is.

    Is the regulator capable of handling the current that you may be getting from an array of 5x180 watt panels if connected in parallel or the voltage from a 5x180 watt array if connected in series?

    Have you blown a fuse on the regulator?
    2011 D4 3.0 SDV6
    1999 D2 V8, in heaven
    1984 RRC, in hell

  4. #4
    Join Date
    Jan 1970
    Location
    Sydney
    Posts
    557
    Total Downloaded
    0
    Hi Ron,

    They are in parallel, I'll check the voltage when we go up to the property on the long weekend.

    I also have a Nationa Luna dual battery monitor connected on them, they max out at 12.6v. The same monitor on my car shows 13.6 when my car and dual is charging when driving. So I kinda expected the same to happen with then solar system. I have some pics and will add them a bit later.

    Cheers

    Jan

  5. #5
    Join Date
    Jan 1970
    Location
    Sydney
    Posts
    557
    Total Downloaded
    0
    Hi,

    Eperver Tracer MPPT, not sure if its the 30Amp or 40Amp unit.

    I'll find out.

    Thanks heaps

    Jan

  6. #6
    Join Date
    Feb 2007
    Location
    Perth
    Posts
    3,807
    Total Downloaded
    0
    Quote Originally Posted by TheEntertainer View Post
    Eperver Tracer MPPT, not sure if its the 30Amp or 40Amp unit....
    5x180 watt panels could produce ~900 watts of power.

    If your 2 batteries were wired in parallel they would require ~14v to charge. If the batteries were to draw a large current during that charging cycle your solar array could potentially supply up to ~64 amps.

    If your regulator handling capacity is only in 30 - 40 amp range then you're are probably a bit 'under gunned' for your purpose.

    A decent regulator will probably protect itself somehow against exceeding it's max rated PV current - fuse or something more sophisticated. The point is it will probably shut down in some manner, hopefully before the excess current destroys it.

    Given the information you have supplied you seem to have a mismatch between rated solar capacity and rated regulator sizing.

    If all the above is indeed the cause of your troubles then you either need to drop out some solar panels to match your regulator sizing (assuming your regulator stills works) or get a bigger regulator.
    2011 D4 3.0 SDV6
    1999 D2 V8, in heaven
    1984 RRC, in hell

  7. #7
    DiscoMick Guest
    Quote Originally Posted by TheEntertainer View Post
    Hi Ron,

    They are in parallel, I'll check the voltage when we go up to the property on the long weekend.

    I also have a Nationa Luna dual battery monitor connected on them, they max out at 12.6v. The same monitor on my car shows 13.6 when my car and dual is charging when driving. So I kinda expected the same to happen with then solar system. I have some pics and will add them a bit later.

    Cheers

    Jan
    Sounds like you're reading the state of the battery, not the input.
    12.6 is a fully charged battery (6 x 2.1). 13.6 is a typical alternator output when the engine is running. Those are normal numbers.
    What is the charging limit the batteries can accept? Might say on the battery.
    The MPPT should adjust to what your batteries can safely accept.
    5 x 180 watt panels is a lot of solar capacity. Maybe too much.

  8. #8
    Join Date
    Jan 1970
    Location
    Sydney
    Posts
    557
    Total Downloaded
    0
    Hi,

    Just had a chat to FIL.

    5 x 100watt.
    2 x AJ-FORCE 200AH deep cycle batteries in Parallel.

    With the sun out I would expect them to charge at 13.6 - 13.8 with the multi meter.

    The epever is a 40amp.

  9. #9
    Join Date
    Feb 2007
    Location
    Perth
    Posts
    3,807
    Total Downloaded
    0
    In that case, your regulator is sized correctly.