Originally Posted by
Vern
power needs to be 600 deep in H/D conduit, you need to install underground power line marking tape at 300 deep on top of the power conduit. Comms stuff in comms conduit at 300 is fine.
Your sparky by law has to label the switchboard anyway, but more than likely he will just put power stickers under the power circuits and light stickers under the light circuits. If you were to label it CB1, then you should label all the applicable power points CB1 etc...
i'd run 6mm2 TPS minimum to your shed, good for 32Amp, possibly 40A depending on how its run.
14A is a big split sytem, or an old one