    You can do the job yourself but you must have the a/c evacuated and then regased when you put it back in.You will see what you have to do when you pull it out in to the open it was surely a poor design.Hope i am of some help next time i will take photos.

  2. #22
    DH Guest
    One of the main causes of the problem is the two a/c drains going into one pipe through the floor. get rid of the t/piece,drill new holes in the floor directly under drains and run new pipes out the floor and the water will get out of the catch tray. I have done this a number of time in the shop and it works.
    Good luck.

  3. #23
    Join Date
    Jan 1970
    Location
    Hobart, Tasmania
    Posts
    897
    Total Downloaded
    0
    Originally posted by DH
    One of the main causes of the problem is the two a/c drains going into one pipe through the floor. get rid of the t/piece,drill new holes in the floor directly under drains and run new pipes out the floor and the water will get out of the catch tray. I have done this a number of time in the shop and it works.
    Good luck.
    Excellent! I'll do that and let everyone know!

    Cheers
    Chris