  1. #201
    Join Date
    Jul 2009
    Location
    Mid North Coast, NSW
    Posts
    1,093
    Total Downloaded
    51.4 KB
    Here is a screenshot of my ac pressure from car off, to start car with ac on full.

    Screenshot_20221231-103201_IIDControl.jpg

  2. #202
    Join Date
    Apr 2008
    Location
    Brisbane,some of the time.
    Posts
    13,886
    Total Downloaded
    0
    Quote Originally Posted by haydent View Post
    Here is a screenshot of my ac pressure from car off, to start car with ac on full.

    Screenshot_20221231-103201_IIDControl.jpg
    Looks fine after the 4 minute mark,but cycling at just over 3000Kpa before that doesn't seem correct?

    But then again last time i played with auto air the systems had a glass and ran on R12.

    See what the others think.You may have another fault that caused the compressor failure.
    What were the ambient temps at the time?

  3. #203
    Join Date
    Jul 2009
    Location
    Mid North Coast, NSW
    Posts
    1,093
    Total Downloaded
    51.4 KB
    Not sure, but when I had it regassed and first started running it the tech said the pressure was a high and asked if it had a thermo fan, i said i thought there was put not sure where. then it kicked in and the pressure became normal, so likely its just this, that the thermo fan hadnt started running yet, i can do another capture with this plotted too.

  4. #204
    Join Date
    Jun 2017
    Location
    Crows Nest Qld
    Posts
    273
    Total Downloaded
    0
    That graph is a bit disturbing. I'd much prefer to see a set of gauges to work out what is actually happening.

  5. #205
    BradC is offline Super Moderator
    No one of consequence
    Supporter
    Join Date
    Mar 2018
    Location
    Perth (near Malaga)
    Posts
    3,545
    Total Downloaded
    0
    Quote Originally Posted by scarry View Post
    Looks fine after the 4 minute mark,but cycling at just over 3000Kpa before that doesn't seem correct?
    The manual says "Increases to 33 ± 1 bar (479 ± 14.5 lbf/in 2 ): the ATCM loads the A/C compressor again when the pressure
    decreases to 23.5 ± 1 bar (341 ± 14.5 lbf/in 2 )." So looks like it's oscillating on the protective limiter.

    I've *never* seen a SCT of >80C even under the worst ambient conditions.
    MY08 D3 - The Antichrist - "Permagrimace". Turn the key and play the "will it get me home again" lottery.

  6. #206
    Join Date
    Apr 2008
    Location
    Brisbane,some of the time.
    Posts
    13,886
    Total Downloaded
    0
    Quote Originally Posted by BradC View Post
    The manual says "Increases to 33 ± 1 bar (479 ± 14.5 lbf/in 2 ): the ATCM loads the A/C compressor again when the pressure
    decreases to 23.5 ± 1 bar (341 ± 14.5 lbf/in 2 )." So looks like it's oscillating on the protective limiter.

    I've *never* seen a SCT of >80C even under the worst ambient conditions.
    As i thought,cycling on the HP switch.

    With 2.7l D4 i could see the revs the fan was doing on the Gap tool,but i am not familiar with the set up on the 3.0L,that is if it is a 3.0L.
    But something is not correct,probably with the fan,air over the condenser is too low,at a guess.It isn't coming on at start when it should be.
    We set our safeties for R404a/R22/448,etc, at 400PSI,run around 280PSI,depending on ambient,and this is 134a

  7. #207
    josh.huber Guest
    I wonder if thats how long it takes the viscous fan to speed up from dead cold?

    It starts off normal, slowly ramps up due to no cooling then slowly comes back down. How long does it take the ECM to heat up the fan and get it moving.. Especially at idle.

    Go for a drive with this log on, include fan command, I'll log mine the same this morning and report back.. It doesn't good.. But it might not be that bad.

  8. #208
    josh.huber Guest
    Ok, just tested my D4.

    On start up the fan was running at 1000rpm.. So basically 1:1. Never went past idle.. Pressures started at 140psi and creeped to 170psi but never any higher..I had the knobs on full cold with the windows down.

    You can do it again watching fan speed or get a hose on mist and cool down the condenser at the same time. Also log other things, my air con saved list on gap has evap temp. Ambient. Pressure valve current etc.

    Start with the fan

  9. #209
    Join Date
    Jul 2009
    Location
    Mid North Coast, NSW
    Posts
    1,093
    Total Downloaded
    51.4 KB
    Here I was thinking it was a separate thermo fan turning on a minute or so after startup, but it must be the viscous ramping up.
    I ran the test again (everything cold) and this time pressure didnt go so high, much more stable, will try again another day. Maybe this time due to ambient temp being a bit lower. Engine is TDV8

    edit: (this graph is a bit off, car was only idled, so fan rpm is wrong and viscous control is not changing, yet fan speed is)

    Screenshot_20230101-190927_IIDControl.jpg

  10. #210
    Join Date
    Apr 2008
    Location
    Brisbane,some of the time.
    Posts
    13,886
    Total Downloaded
    0
    Viscous fan may also have an electric overide,but i dont know how it operates,or what controls it.

    At idle,to get the head pressure up to those sorts of pressures i would presume virtually no air would be going over the condenser.