Originally Posted by
drivesafe
Hi 350RRC, if I were you, while the 8G cable is fine but I’d replace the 50 amp fuse with a 30 amp auto resetting circuit breaker. This will give you both short circuit protection as well overload protection.
8G or 8B&S cable ( 7.9mm2 ) has a maximum continuos load rating of 65 amps and a 50 amp fuse is actually designed to carry 135% of its marked rating for around 30 minutes. Thats 67.5 amp, and high amps for shorter periods.
Those rates are just to much to be safe and even if you run a few things at the same time, it highly unlikely that you will continually pull 30 amps.
I would also fit at least 15 amp but 20 amp fuses would be the best protection for each power socket. 20 amp fuses will still blow if there is a short circuit and while 10 amp fuses will blow a split second quicker, they will run hot and could melt if you use any appliance that pulls 8 to 10 amps.