Your making this all far too hard. P, I & D setting have no effect whatsoever on the temperature measurement. They effect the response of the output of the device when it's being used as a controller. You are (I presume) using the device only to display a measured temperature input.
There may be a parameter in the set-up menus to adjust the level a filtering or damping applied to the measurement input. This will after the speed of response of the display to temperature changes and would normally be set to the minimum value for EGT display. But it can never be faster than the inherent response of the EGT thermocouple itself, which will usually have a time constant of several seconds. This is OK and very much quick enough for EGT measurement.
If you can post a link to the instruction sheet, I'll see if I can spot the right parameter to look at.
Hope this helps,
Ian (aka ThermoGuard)