    A new one for fridgies

    I'm trying to commission a new a/c system in my RRC and when it was given to shop they couldn't get R134a into high pressure side. This is brand new never used system first time to attempt charge. It's a vintage air gen11 unit with York compressor brand new old stock with vintage air condenser. I've got electric fans with a trinary switch. I've found two things - I had condenser in upside down yeah I know my bad so had Lp side on bottom. And I think the new trinary switch "which has build date 2013" may also be no good. It's open circuit at all times on all circuits I thought the hp side should be closed circuit. So - if the trinary switch was u/s would that prevent hp side of circuit charging? Or is it simply because the condenser was upside down?

  2. #2
    Join Date
    Jan 1970
    Location
    NSW far north coast
    Posts
    17,285
    Total Downloaded
    0
    Naa, you have a blockage of some description, probably in the service valve itself.
    I'd remove the Schrader core in the high side fitting.
    Are there any other service ports in the high side?
    E.g.. On the drier or in the liquid line?

  3. #3
    Join Date
    Oct 2011
    Location
    Sunshine Coast
    Posts
    1,224
    Total Downloaded
    0
    Thanks I found the problem myself today. There's the original valves/gauge ports on suction/discharge ports of the compressor. To make access easier I'd fitted Schroder valves on low and High pressure hoses. But- the A/C "experts" I'd given car to forgot about these valves which were in closed position and tried to charge unit with both valves closed. That's never going to work. I suspect they didn't know what they were. Needless to say going elsewhere Monday A new one for fridgies

  4. #4
    Join Date
    Oct 2011
    Location
    Sunshine Coast
    Posts
    1,224
    Total Downloaded
    0

  5. #5
    Join Date
    Jan 1970
    Location
    NSW far north coast
    Posts
    17,285
    Total Downloaded
    0
    Standard Rotolock service valve.
    Still in common usage and used on new compressors, just not automotive.

  6. #6
    Join Date
    Apr 2008
    Location
    Brisbane,some of the time.
    Posts
    13,888
    Total Downloaded
    0
    Quote Originally Posted by rick130 View Post
    Standard Rotolock service valve.
    Still in common usage and used on new compressors, just not automotive.
    Not as common as they used to be in auto air,but everywhere else there are literally millions of them.

    I keep wearing my ratchets out on them.

  7. #7
    Join Date
    Oct 2011
    Location
    Sunshine Coast
    Posts
    1,224
    Total Downloaded
    0
    Yeah well they completely missed them and they are in plain sight 100mm lower down from the connections in hoses. What to say lah?